Specyfikacja

  • Application

    Clean steam, hot condensate, water,
    WFI and other liquids and gases

  • Body material

    Stainless steel AISI 316L

  • Max. allowable pressure

    10 bar

  • Min. operating pressure

    Spring (Standard),
    Without spring (only for vertical installation,
    with upwards flow), on request,
    5 mbar, on request,
    100 mbar, on request.

  • Max. operating temperature

    200 ºC

  • Body sealing

    PTFE – Tmax 200 ºC,
    EPDM* HP – Tmax 150 ºC,
    (*) Tmax 180 ºC with steam and hot water

  • Standard surface finish

    External: ≤ 0,76 µm Ra – SF3,
    Internal wetted parts: ≤ 0,51 µm Ra – SF1.

  • Installation

    Vertical

  • Connections

    Clamp ferrules ASME BPE,
    Tube weld (ETO) according to ASME BPE

ADCA® Sanitary Check Valve ADCAPure SRTV10 In-Line, vertical

Kod produktu: SRT.V.X.T000S

Dostępne na prośbę

Cena zgodnie z konfiguracją

Wybierz konfigurację
Zobacz wszystkie konfiguracje
Ref.#.
Bez VAT
(ORIENTACYJNA CENA)

Ilość

-
+

Brak konfiguracji produktu

DESCRIPTION

The ADCAPure SRT10 all stainless steel disc check valve has a compact design and is specially designed for use with clean steam, hot condensate, WFI and other process fluids.
These valves are particularly recommended for use in high purity applications found in the pharmaceutical, fine chemical and cosmetic industries.

MAIN FEATURES

Compact design. Spring loaded.
Low friction stem guiding.
Completely machined from bar stock material, no castings or forgings are used on the standard version.

STANDARD SURFACE FINISH

Internal wetted parts: ≤ 0,51 µm Ra – SF1.
External: ≤ 0,76 µm Ra – SF3.
Other surface conditions see on request.
Ultrasonic cleaning.

AVAILABLE MODELS

SRTV10 – vertical installation.

OPERATION

The valve is opened by the pressure of the fluid. When fluid flow stops the spring closes the valve before reverse flow can occur.