Napisz do nas request@prima-steam.com
Język

PL

Dom → Katalog → Urządzenia parowe → Odwadniacze → Automatical condensate drain valve ADCA CDV32

Specyfikacja

  • Description

    Condensate drain valve automatically discharges air and condensate from steam systems during start-up

  • Application

    Saturated and superheated steam,
    steam condensate

  • Body material

    Carbon steel

  • Max. operating pressure

    22 bar

  • Min. working pressure

    0,1 bar

  • Max. operating temperature

    250 ºC

  • Flow rate capacity

    Up to 780 kg/h

  • Closing pressure

    Delta P: 1,5 bar

  • Connections

    Female threaded ISO 7 Rp (NPT on request),
    Flanged EN 1092-1 PN 40,
    Flanged ASME Class 150 or 300 on request,
    Socket weld (SW) ASME B16.11 on request

Documentation

Technical data sheet(s)

Automatical condensate drain valve ADCA CDV32

Kod produktu: CDV32

Dostępne na prośbę

Cena zgodnie z konfiguracją

Wybierz konfigurację
Choose on Option...
  • Gwintowane
  • Kołnierzowe
Choose on Option...
  • 1/2"
  • 3/4"
  • 15
  • 20
Choose on Option...
  • ≈ 1.5 bar
Zobacz wszystkie konfiguracje
Ref.#.
Bez VAT
(ORIENTACYJNA CENA)

Ilość

-
+

Brak konfiguracji produktu

Zobacz wszystkie konfiguracje

Model Przyłącza Wielkość Closing pressure Ref Cena Ilość
Automatical condensate drain valve ADCA CDV32 BSP 1/2" DP=1.5 bar Gwintowane 1/2" ≈ 1.5 bar CDV32.T015
-
+
Automatical condensate drain valve ADCA CDV32 BSP 3/4" DP=1.5 bar Gwintowane 3/4" ≈ 1.5 bar CDV32.T020
-
+
Automatical condensate drain valve ADCA CDV32 DN15 DP=1.5 bar Kołnierzowe 15 ≈ 1.5 bar CDV32.F015
-
+
Automatical condensate drain valve ADCA CDV32 DN20 DP=1.5 bar Kołnierzowe 20 ≈ 1.5 bar CDV32.F015
-
+

The CDV32 condensate drain valve automatically discharges air and condensate from steam systems during start-up. A compression spring keeps the valve open when the system is not pressurized. As soon as the operating pressure reaches the closing pressure to which the CDV is set, the valve closes. If the operating pressure drops below the closing set pressure, the spring force will cause the CDV32 to open once again.

Dokumentacja

Karta(y) charakterystyki technicznej

← Back to list